125 HP, Cleaver-Brooks, 30 PSI,
Location:
Fremont, CA
Manufacturer:
N/A

Specifications

Condition:
used
Stock number:
482
Drain:
1½" NPT
#2 oil:
37.5 GPH @ 2 psig
Length:
14' 11"
Natural gas:
5,100 SCFH @ 3-15 psig
#2 oil return:
½" NPT
#2 oil supply:
½" NPT
Natural gas 2:
3"-150# FLG
Shipping weight:
14,900 lbs
Hot water return:
6"-150# FLG
Hot water supply:
3"-150# FLG
Width (incl. hw pump):
8' 9"
Height (floor to piping):
10' 0"
Subcategory:
Electrical power

Description

Nationwide Boiler’s 125 hp (4,312 lbs/hr) skid-mounted Cleaver-Brooks hydronic heating firetube boiler is designed at 30 psig pressure, firing natural gas or #2 oil. It is fully piped and wired
nd includes the following components:
125 hp Cleaver-Brooks Hydronic Heating Boiler
Burner
Pilot Ignition System
Honeywell RM7800 Flame Safeguard w/ Display Module
Dual Low Water Cutoffs
Pressure Gauge
Safety Pressure Relief Valves
Hot Water Supply & Return Isolation Valves (installed)
Drain Valves (installed)
Hot Water Supply Pump (7.5 hp, 190 gpm @ 60' TDH)
Fused Disconnect Switch
#2 Fuel Oil Pump
Forced Draft Fan, Motor & Starter
Stack (loose)
Meets FM / IRI Insurance
Operating Manuals
Fuel Consumption:
Natural Gas: 5,100 SCFH @ 3-15 psig
#2 Oil: 37.5 GPH @ 2 psig
Connection Sizes:
Hot Water Supply: 3"-150# FLG
Hot Water Return: 6"-150# FLG
Natural Gas: 3"-150# FLG
#2 Oil Supply: ½" NPT
#2 Oil Return: ½" NPT
Drain: 1½" NPT
Electrical Power Service Requirements:
480 VAC, 3 ph, 60 hz, 50 amp
Dimensions & Weights:
Length: 14' 11"
Width (incl. HW pump): 8' 9"
Height (floor to piping): 10' 0"
Shipping Weight: 14,900 lbs