Top Seller
DIVERSI-TECH FRED™ T SERIES 3000
Location:
Port Orange, FL
Manufacturer:
DIVERSI-TECH
Model:
FRED™ T SERIES

Specifications

Condition:
new
Stock number:
T-3000
T-3000:
3/4HP 115/1/60 PSC Type 3000 cfm @ .6" W.G. 15" x 72" x 25" 150 Lbs 10x10 Forward Curve Blower: Direct Drive 2-4" Pleated Prefilters - 2-95% Bags/64 Sq. Ft.
T-3500:
2HP 230/460v/3/60 115v (option) 3500 cfm @ .75" W.G. 25" x 72" x 25" 170 Lbs 10 x10 Forward Curve Blower: Belt Drive 2-4" Pleated Prefilters - 2 - 95% Bags/80 Sq. Ft
T-4500:
3HP 230/460v/3/60 4500 cfm @ .8" W.G. 25" x 72" x 25" 170 Lbs 10x10 Forward Curve Blower: Belt Drive 2-4" Pleated prefitlers - 2- 95% Bags/80 Sq. Ft.
T-6000:
5HP 230/460v/3/60 6000 cfm @ .75" - 1,200 rpm 25.5" x 82" x 51" 315 Lbs 12x12 Forward Curve Blower: Belt Drive 4-4" Pleated Prefilters - 4-95% Bags/80 Sq. Ft.
T-7500:
5HP 230/460v/3/60 7500 cfm @ .75" - 1,200 rpm 51.5" x 82" x 51" 520 Lbs. 12x12 Forward Curve Blower: Belt Drive 8-4" Pleated Prefilters - 8-95% Bags/80 Sq. Ft.
Warranty:
1 YEAR

Description

ITEM: 3000 - 7500 cfm Ambient Air Filtration Systems
MAKE: DIVERSI-TECH®
MODEL: FRED™ T SERIES
PART# T-3000 / T-3500 / T-4500 / T-6000 / T-7500
Product Features
FRED - F iltration, R eusable filters, E nergy savings, D ramatically reduced pollution
Diversi-Tech's FRED™ T Series Packaged Air Filtration Systems are designed to collect dust, smoke, and other airborne particulates with a 95% efficient, 2- stage filtration system. The unit's modular construction is designed as part of a complete ambient air filtration package. Units can be stacked in a number of vertical, horizontal, or quad configurations. Simple field modification of the assemblies allows for an easy way to lower your air-to-cloth ratio for demanding applications
Welding Smoke and Fumes
Wood Dust
Oil Mist and Smoke from Machining
Dust from Grinding
How The FRED™ Filter System Works: The use of a T Style air cleaner configuration offers some key advantages for "ree hanging" air filtration applications
Dual intake - twice the normal intake area of a straight through air cleaner (more intakes help create a better airflow pattern)
Dual filters - nearly twice the filter media of a straight through air cleaner (longer filter life & filter service intervals)
Clean air throw is at 90 degrees from the intakes allowing for a better air pattern through the work space (a factory wall can be used as a barrier to help direct dirty air into the intakes)
Options/Accessories
Silencer Eyebolts
Magnahelic Gauge
Minihelic Gauge
Manometer
Carbon Vbank Odor Control Filter Modules